How efficient could your heat pump be in an ideal world?

How efficient could your heat pump be in an ideal world?

There are only a couple of rules that actually make any sense, mostly because they were not written by politicians. The one I want to explore today is the theoretical efficiency from a heat pump.

A heat pump is just a machine which has the ability to move heat and therefore lift the temperature from one place to another using a refrigerant and a pump. Your fridge does it, it sucks heat out of your frozen pizza and moves it out the back and heats your kitchen. Moving or pumping heat is not creating any energy, its just moving it.

There is a formula for working out what the absolute theoretical efficiency you can achieve if the heat pump is perfect and has no friction etc. Its called the Carnot efficiency, Carnot discovered this rule, he did not write it, its a law of physics and is totally unbreakable. Carnot did not work for a manufacturer of heat pumps and wasn't a marketeer. The formula is pretty simple:

The maximum achievable efficiency is the temperature of the hottest part of the system (+273 because they loved Kelvin as a temperature scale back in the day) divided by the difference in temperature between the hottest bit and the coldest bit.

example:

My heat pump is working at 10C outside, which is 283K, inside its heating the water to 40C or 313K. The efficiency in theory could be 313/ (313-283) = 10.4

No alt text provided for this image

Great news for marketeers, but its not completely true. The problem is if its 10C outside the heat pump has to work at a slightly lower temperature to absorb the heat, remember hot goes to cold. So we run our heat pump coil at 2C when its 10C outside. The same is true for the inside part heating the water. To make water at 40C we have to run the heat pump at a higher temperature something like 43C. So now the formula changes to:

efficiency in theory could be 316/ (313-275) = 7.7

No alt text provided for this image

That's more like it. But Carnot didn't have to worry about powering water pumps, printed circuit boards, crankcase heaters or fan motors and he assumed compressor efficiency was 100%. There is no way you can get anything like this good efficiency in these conditions. It would be more reasonable to achieve a COP of 5 from any heat pump running in the conditions listed above.

Now here's the fun bit. In the UK we do not have to measure or report the efficiency of any heating device accurately. There is no boiler anywhere which actually measures the flow rate through the boiler, the heat produced and the gas consumed. And they definitely dont measure how much electricity the boiler uses to provide your heating. In fact you just assume your efficiency based on the fictional figures you are given when you buy the boiler. 90% efficiency is apparently, that is a triumph of marketing.

We in heat pump land are a bit better than that, but we are not perfect, we use some devices which help the figures. Its common now in heat pumps to measure energy in and heat out and give you a COP figure on screen. But most heat pumps only measure the power drawn by the compressor, we conveniently forget about the controls, pcb, fans, pumps etc. so the figure is reported slightly higher than is real.

You could put special dedicated heat meters on the pipework and measure the actual energy the whole system uses and get a really accurate figure for COP, but its not a requirement and is strictly for geeks. Back in the RHI days there was a programme called MMSP, it was horrible, you were paid a bit more RHI to install proper metering on the system. It was ridiculously complex and expensive, the heat meter was hundreds of pounds and made of solid Gold. I had one for a few weeks, it stopped working and no one noticed.

So the point is be careful when you see any COP claim which looks high, if it looks high it probably is not completely true. Most heat pumps today can achieve a COP averaged across a whole year of about 4 if they are set up well with properly adjusted weather compensation running maximum temperatures up to 50C on radiators. With under floor heating you might see high 4s, underfloor heating runs at lower temperatures.

If you flog the units to death at high temperatures all the time the COP falls.

I hope you enjoyed this, this isn't in my new book 50 things heating professional need to know about heat pumps, but it might be in the third one out in the Autumn.

No alt text provided for this image









https://dothemath.ucsd.edu/2012/06/heat-pumps-work-miracles/#:~:text=For%20instance%2C%20the%20theoretical%20efficiency,of%207%E2%80%94half%20as%20good.

Graham Hendra

Heat Pump Subject Matter Expert, Refrigeration and Air conditioning lecturer

11mo

I just read this again. I hoped it would kill off all the ridiculous cop claims people make. I guess I was over ambitious. Cop of 8 anyone, sorry I'm falling about laughing.

Like
Reply

What about an article with good practices / advices on how to run efficiently an oversized heat pump. In my country, many sellers sell oversized pumps and us, the users, are facing a sad reality or trying our best to make them efficient. Thank you for great articles and advice.

Like
Reply
William Johnson

Mechanical Engineer, Heat Pump Specialist

1y

Nice piece Graham few people actually get further than the marketing blurb and like to believe what they read rather than actually think about the figures. In fact, this is critical in understanding the difference between one HP and another. I feel you missed a chance to point out that the size of the heat exchanger plays a part in the efficiency; the bigger it is, the smaller the temperature difference. A smaller temperature difference gets the gas closer to the ideal Carnot cycle. Smaller, cheaper, heat pumps are usually less efficient.

Steve Green

Green Chemical Engineer

1y

Article wont open for me but wondered you've tried tracking Carnot COP efficiency for various heat pumps. I.e. Actual COP divided by Theoretical Carnot COP, (allowing for condensing and vapourising delta Ts) Some of us worked it out for an operating Mitsi and it was about 50% Seems like one of many ways to compare heat pumps

Craig Baker

Director of Technical at Kensa Contracting

2y

I can show you a SCOP above 7, but that is overall system efficiency of a simultaneous heating and cooling set up, so don’t shoot me 😂

To view or add a comment, sign in